Institutional Tuberculosis Transmission. Controlled Trial of Upper Room Ultraviolet Air Disinfection: A Basis for New Dosing Guidelines

112

Citations

30

References

2015

Year

Abstract

Upper room germicidal UV air disinfection with air mixing was highly effective in reducing tuberculosis transmission under hospital conditions. These data support using either a total fixture output (rather than electrical or UV lamp wattage) of 15-20 mW/m(3) total room volume, or an average whole-room UV irradiance (fluence rate) of 5-7 μW/cm(2), calculated by a lighting computer-assisted design program modified for UV use.