IEEE Transactions on Power Apparatus and Systems · 1963 · 30 citations · 5 references
EngineeringElectrical EngineeringSoil MechanicsSoil PhysicsSoil ScienceElectrical Conductivity Of SoilsElectrical Resistivity MethodsElectrical Resistivity Of SoilsGround Resistance MeasurementGroundingGrounding SystemsResistivitySoil Electrical Conductivity EstimationSoil Resistivity
High‑voltage switchyards typically use a grid of horizontally buried conductors for basic grounding. The study develops a method to more accurately determine the resistance of grounding grids. The method models typical grid dimensions and depth‑dependent soil resistivity laws to compute grounding resistance. Computed resistance values agree well with measurements from operating substations.
ln most high-voltage switchyards, basic grounding systems are formed by a grid of horizontally buried conductors. A method is developed to determine more accurately the resistance of such grounding systems. The dimensions are those usually encountered in practice with the conductors buried near the surface of the earth. The varying soil resistivity may either increase or decrease with depth according to a certain law, which can represent most of the soil conditions that normally occur in practice. The computed results check well with data obtained from tests in substations which are in service.
5
Efficiency of grounding grids with nonuniform soil