IEE Proceedings C Generation Transmission and Distribution · 1993 · 12 citations · 0 references
EngineeringElectrical EngineeringElectric MachinesEnergy SystemsPower ElectronicsConverter TopologiesDc-dc ConversionDc-dc ConvertersGenerator OperationHigh-frequency Power ConversionPower QualityExperimental Results InterpretationHarmonic ReductionHigh-frequency Dc-dc ConversionOutput Harmonic ReductionPulse GeneratorsRipple ReductionRipple Reduction TechniquesTotal Harmonic Distortion Reduction
A method of increasing the pulse number of an HVDC convertor based on the reinjection of the DC ripple is applied to a unit-connected generator-convertor scheme operating at variable speeds. Theoretical and experimental results are provided which demonstrate that, with the proposed modification, a single-bridge configuration can be made to operate as an 18-pulse convertor for a wide range of generator frequencies.