Journal of Heat Transfer · 1998 · 44 citations · 10 references
EngineeringMechanical EngineeringFluid DynamicsHeat TransferThermal AnalysisDuct DesignHeat ExchangersHeat FlowHeat Transfer AnalysisHeat Transfer In FluidsThermal DesignCompact Heat ExchangersHeat Transfer EnhancementHeat Transfer In DuctsHydraulic PerformanceRectangular Duct DesignReynolds NumberSwirl FlowThermal Performance Of Ducts
Experiments have been carried out to investigate the performance of a new swirl flow duct which is suitable for compact heat exchangers such as radiators. The ducts tested have rectangular cross sections with aspect ratio 1 to 8, and multiple V-shaped ribs are attached to the wide walls in a staggered arrangement such that square secondary flow cells are established. A previous investigation has shown that multiple V-shaped ribs may provide greater heat transfer enhancement than angled straight ribs and V-shaped ribs at Reynolds numbers below 2000. The data are presented as j and f factors for Reynolds numbers from 500 to 15,000, and correlations are obtained for the influence of rib height (0.1 < e/H < 0.2), rib pitch (3 < p/H < 7), and rib angle (15 deg < Φ < 45 deg). It was found that a rib angle of 45 deg provided the highest j/f ratio, while increasing the rib height or decreasing the rib pitch lowers the j/f ratio.