IEEE Transactions on Power Electronics · 2013 · 199 citations · 39 references
EngineeringElectrical EngineeringEnergy SystemsPower ElectronicsRenewable Energy SystemsFrequency ControlPower Grid AnalysisPower System StabilityPower SystemsSmart GridsVoltage RegulationGrid SynchronizationGrid-connected InvertersIslanded OperationIslanded Power SystemsLoad Voltage RegulationVoltageVoltage ControlVoltage Sag Mitigation
This paper proposes a phase-locked loop (PLL)-based seamless transfer control method between grid-connected and islanding modes in a three-phase grid-connected inverter. The PLL is used to synchronize the phase of the load voltage to a grid voltage in grid-connected operation, and to generate an angle with the desired frequency in islanding operation. The stability of both the grid current loop for grid-connected operation and the load voltage control loop for islanding operation is analyzed. The phase and magnitude of the load voltage are successively matched to the grid voltage for a seamless transfer from islanding to grid-connected operation. When grid voltage sag occurs, an operating sequence including a PLL operation is suggested in order to transfer smoothly to islanding operation and to provide a stable and seamless voltage to a sensitive load under the voltage sag condition. The simulation and experimental results are carried out to verify the effectiveness of the proposed algorithm.
39
Pedro Rodríguez, Álvaro Luna, Raúl Santiago Muñoz Aguilar et al. · IEEE Transactions on Power Electronics · 2011 · 668 citations
Benjamin Kroposki, R.H. Lasseter, Toshifumi Ise et al. · IEEE Power and Energy Magazine · 2008 · 637 citations · Full text
Engineering, Electrical Engineering, Distributed Systems +16