EngineeringElectrical EngineeringPhysicsElectromagneticsElectromagnetismPower ElectronicsElectrical InstallationElectrical SafetyElectrical System TestingElectromagnetic CompatibilityProtection SystemsRadio Frequency Interference MitigationElectromagnetic InterferenceElectromagnetic Interference ControlElectromagnetic Interference ManagementElectromagnetic Interference MitigationElectromagnetic Interference ReductionElectromagnetic Interference SuppressionSurge Protective DevicesSwitching Surges
Thyristor malignitions and protector relay failures caused by gas circuit breakers closing in the gas insulated switchgear (GIS) of a power cable system could not be controlled by reducing the ground impedance or adding surge absorbing capacitors. As a result, a study was carried out on this problem with a 66 kV mock-up apparatus installed in a factory. It was found that malignitions and failures such as those mentioned above could be controlled by preventing 10 MHz ultra high-frequency surges emitted by the GIS from leaking out into the grounding system.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>