Investigation of a respiratory disease associated with an air‐conditioning system

Christopher Pickering, Willie Moore, J. Lacey, V. Holford-Strevens, J. Pepys

Clinical & Experimental Allergy · 1976 · 78 citations · 5 references

Concepts

Abstract

This paper describes the investigation of respiratory disease presenting in a group of men employed on the printing floor of a factory. The air-conditioning units supplying this floor were found to be contaminated with a variety of micro-organisms. The specific cause of the disease was not identified but an alteration in the system of humidification led to the complete resolution of symptoms.