Earthquake Spectra · 1996 · 12 citations · 0 references
EngineeringCivil EngineeringEarthquake EngineeringStructural DynamicsVibrationDamped VibrationDynamic StiffnessStructural DampingStructural VibrationVibration AnalysisCircuit DampingDampingDamping RatiosFriction DampersGround Acceleration ResponseNatural Frequency AnalysisPeak Ground AccelerationStiffness
The design parameter of 1.05 g peak seismic ground acceleration for a 300 kV SF6 circuit breaker necessitated the provision of supplemental friction‐based dampers. This paper describes the dampers and the dynamic properties of the circuit breaker as obtained from a series of pull‐release tests with increasing force amplitudes. These tests permitted a determination of a wide range of damping ratios and natural frequencies as a function of displacements. A comparison is also presented between the measured and the calculated damping ratios and frequencies, using common engineering approximation of the energy dissipated per cycle for damping, and a discrete parameter and linearized stiffness approach for the calculation of natural frequency. Reasonable comparisons were achieved between the measured and calculated values.