IEEE Transactions on Power Electronics · 2014 · 171 citations · 29 references
EngineeringElectrical EngineeringAnalog ElectronicsFault-tolerant SystemsPower ElectronicsAc-dc ConvertersDc-dc ConvertersMicrogridsMultilevel ConvertersPower System StabilityVoltage RegulationCurrent ControlEquivalent Circuit AnalysisEquivalent Circuit ModelingFault Tolerant OperationHvdc TransmissionModular Multilevel ConvertersMultilevel Dc-dc ConverterThree-phase Multilevel Converters
This paper presents the analysis and control of a multilevel modular converter (MMC)-based HVDC transmission system under three possible single-line-to-ground fault conditions, with special focus on the investigation of their different fault characteristics. Considering positive-, negative-, and zero-sequence components in both arm voltages and currents, the generalized instantaneous power of a phase unit is derived theoretically according to the equivalent circuit model of the MMC under unbalanced conditions. Based on this model, a novel double-line frequency dc-voltage ripple suppression control is proposed. This controller, together with the negative- and zero-sequence current control, could enhance the overall fault-tolerant capability of the HVDC system without additional cost. To further improve the fault-tolerant capability, the operation performance of the HVDC system with and without single-phase switching is discussed and compared in detail. Simulation results from a three-phase MMC-HVDC system generated with MATLAB/Simulink are provided to support the theoretical analysis and proposed control schemes.
29