IEEE Electrical Insulation Magazine · 1993 · 29 citations · 16 references
EngineeringElectrical EngineeringElectric MachinesHeat TransferThermal AnalysisCondition MonitoringInsulation MaterialsInsulation SystemsMachine WindingsService LifeThermal InsulationCondition Monitoring Of InsulationInsulation AgingInsulation DiagnosticsInsulation MonitoringInsulation Systems For WindingsMachine Winding InsulationStator WindingsThermal Insulation Systems
The condition of the insulation system frequently limits the useful life of the windings of a rotating machine. This is a function of thermal, electrical, environmental, and mechanical factors plus the type of duty to which the machine is subjected. The thermal classifications of the variety of insulating materials that make up an applied insulation system are presented. Strand and turn insulation, common groundwall insulation systems, armor tapes and coatings, side packing and wedging methods, are discussed. Four factors that influence insulation life are identified: thermal, electrical, ambient (environmental), and mechanical plus performance (intended) and duty (mode of operation). Finally, accelerated aging tests, inspections and diagnostic test during service outages, and online monitoring of partial discharges are discussed.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
16