MAIN BIRD EXCREMENT CONTAMINATION TYPE CAUSING INSULATOR FLASHOVERS IN 110 kV OVERHEAD POWER LINES IN ESTONIA; pp. 211–224

Paul Taklaja, Rein Oidram, Jaan Niitsoo, Ivo Palu

Oil Shale · 2013 · 10 citations · 0 references

DOIFull text

Open access

Concepts

Abstract

The study aims to elucidate which type of bird excrement contamina­tion causes insulator flashovers in 110 kV overhead power lines in Estonia. Laboratory wetting and bird streamer tests performed on naturally contaminated glass and composite insulators show that most likely the flashovers are caused by highly conductive bird excrement streamers and that insulator properties have little influence, if any, on the generation of this kind of contamination driven flashovers.