IET Generation Transmission & Distribution · 2007 · 54 citations · 17 references
EngineeringElectrical EngineeringEnergy SystemsPower ElectronicsProcess ControlFrequency ControlFrequency RegulationPower ControlPower System StabilityActive ControlGainInterconnected Power System Frequency ControlInterconnected Power SystemsPhase AnglePower OscillationsPower System ControlPower System Frequency Dynamics
The analysis of automatic generation control of a two-area interconnected hydrothermal power system considering a thyristor-controlled phase shifter (TCPS) in series with the tie-line is presented. It is possible to damp the system frequency and tie-power oscillations by controlling the phase angle of TCPS. A control strategy using TCPS is proposed to provide active control of system frequency. Gain settings of the integral controllers with and without considering TCPS are optimised using integral squared error technique following a step load disturbance in each of the areas by minimising a quadratic performance index. Analysis reveals that a TCPS is quite capable of suppressing the frequency and tie-power oscillations effectively under the occurrence of sudden load changes in any of the areas when compared with that obtained without TCPS.
17
Understanding automatic generation control
N. Jaleeli, L.S. VanSlyck, D.N. Ewart et al. · IEEE Transactions on Power Systems · 1992 · 706 citations