Stressing of Large Turbine-Generators at Shaft Couplings and LP Turbine Final-Stage Blade Roots Following Clearance of Grid System Faults and Faulty Synchronisation

T.J. Hammons

IEEE Transactions on Power Apparatus and Systems · 1980 · 25 citations · 2 references

Concepts

Abstract

The paper examines transient torque phenomena which can arise at LP turbine blade roots and at shaft couplings of large synchronous-generators following a grid network disturbance. Fault clearance and faulty synchronisations for two 3000 rpm 660 MW turbines and a 3600 rpm, 300 MW turbine is examined. Peak torque at various shaft locations and at the LP turbine final-stage blade roots is computed as a function of the fault clearing time or the synchronising angle respectively. Stresses induced at LP turbine blade roots where the shaft system is protected against excessive stress by use of a turbine/generator shearing coupling is examined for one turbine only. Sustained 3-phase and line-to-line faults at the generator stator terminals are also considered.

References

2