2009 · 28 citations · 1 references
EngineeringElectrical EngineeringAnalog ElectronicsCircuit TheoryPower ElectronicsActive FiltersPower QualityActive FilteringActive Harmonic FilteringHarmonic MitigationHarmonic ReductionHarmonic SpectraShort-circuit AnalysisShort-circuit CurrentTotal Harmonic Distortion Reduction
The harmonic content of the short circuit current during single-phase to earth fault is discussed in networks with compensated neutrals. An overview of different methods to decrease the harmonics in the fault current is given. The zero sequence active filtering method is analyzed in detail using computer simulations. Two compensation algorithms are compared based on their efficiency when operation is maintained during a single-phase to earth fault. Finally, a report of on-site measurements is presented, the measurement results are compared to the simulation results. Based on these results it is concluded that the method has proven to be effective in reducing the residual current and thus it is ready to be implemented in substations.
1