IEEE Transactions on Dielectrics and Electrical Insulation · 2013 · 145 citations · 14 references
EngineeringElectrical EngineeringPhysicsElectrochemical EngineeringPlasma PhysicsPower ElectronicsHigh-frequency Power ConversionHigh-frequency Time Series AnalysisDirect Current DischargesDischarge ProcessesFrequency Spectrum AnalysisPartial DischargePartial Discharge TestingPulse CharacteristicsPulse CharacterizationRise Time
This paper focuses on the influence of repetitive square wave voltage rise time on partial discharge pulse characteristics in the ultra-high frequency range. Paerial Discharge (PD) tests on single-point contact crossed pairs were carried out using repetitive square wave voltages with a wide range of rise times, from 200 ns to 400 μs, including also 50 Hz sinusoidal voltage waveforms. Experimental results show that rise time has a significant influence on magnitude and frequency spectrum of PD pulses. Voltages of shorter rise times generate larger PD pulses with a predominance of high frequency components in the energy spectrum. Interpretations are presented for this phenomenon.
14