Interruption ability of vacuum interrupters subjected to axial magnetic fields

C. W. Kimblin, R. E. Voshall

Proceedings of the Institution of Electrical Engineers · 1972 · 103 citations · 4 references

Concepts

TL;DR

The study power‑tested two 7 cm‑diameter vacuum interrupters with and without an axial magnetic field of 2×10⁻⁵ T per arcing ampere during 10–25 kA arcs to assess its influence on arcing behavior. The axial magnetic field reduced peak arc voltage by ~30% at 0.4 cm spacing, raised the current‑interruption capability of one interrupter by ≥20% and increased the interruption probability of the other, effects attributed to plasma confinement that lowers input power and raises the anode‑spot threshold, also decreasing arcing to the vapour‑condensation shield.

Abstract

Two vacuum interrupters equipped with 7 cm-diameter electrodes have been power tested with and without the presence of an axial magnetic field during arcing. The field strength was 2×10−5 teslaper arcing ampere, with a negligible field at a current zero. Observations with both interrupters at arc currents of 10–25 kA (r.m.s.) revealed that the field suppressed the peak arc voltage at electrode spacings of approximately 0.4 cm by about 30%. The current-interruption ability of one interrupter increased by at least 20%, and the magnetic field also increased the interruption probability of the second interrupter. These effects are attributed to plasma confinement by the field, which reduces the total input power to the interrupter and increases the threshold current associated with anode-spot formation. The plasma confinement also reduces the probability of arcing to the vapour-condensation shield.