Impulse testing of power transformers – a model reference approach
37
Citations
6
References
2004
Year
Fault DiagnosisEngineeringDiagnosisObjective ClassificationPower ElectronicsCondition MonitoringReliability EngineeringFault AnalysisElectric Power TransmissionElectric Power QualityPower System TransientPower SystemsPower System AnalysisPower Electronic DevicesElectrical EngineeringStructural Health MonitoringPartial Discharge EventsImpulse TestingAutomatic Fault DetectionElectrical TransmissionImpulse TestsFault Detection
An objective classification of faults that can occur during impulse tests on power transformers is proposed. It includes nonlinear elements, breakdown, and partial discharge events. An analysis of a layer winding in the time and frequency domains with these faults shows that current assessment methods must be used with caution. A model reference approach is proposed to distinctly improve recognition in such cases. The method is immune to changes of wave shape and the instant of fault is available by observation.