Overvoltages in power transformers caused by no-load switching

G.C. Paap, A.A. Alkema, L. van der Sluis

IEEE Transactions on Power Delivery · 1995 · 49 citations · 5 references

Concepts

Abstract

When an unloaded power transformer is switched on via a relatively long cable, sometimes extreme high voltages appear at the secondary side of the transformer. These overvoltages are caused by a resonant phenomenon that occurs when the resonant frequencies of the transformer and the cable match. The resonant frequency of the cable feeder is equal to the reciprocal of 4 times its travel time /spl tau/. The resonant frequency of the transformer is determined by its short-circuit inductance and the capacitance which is connected to the secondary winding. In this paper a model of this phenomenon is presented and an example of this resonant phenomenon, leading to the insulation breakdown at the secondary side of a power transformer, is given.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>