IEEE Transactions on Power Apparatus and Systems · 1973 · 19 citations · 2 references
EngineeringElectrical EngineeringCircuit TheoryPower ElectronicsReactor PhysicsCurrent Measurement InstrumentsElectrical MeasurementElectrical MetrologyLoss QuantificationReactor InstrumentationBridge Methods In Electrical MeasurementCurrent MeasurementShunt Measurement
The application of a high voltage capacitance bridge based on the current comparator to the measurement of the loss angle of high voltage shunt reactors is described. Measurements on three core-less 55 MVA, 735 kV single phase shunt reactors are discussed and a comparison is made with the results of a calorimetric determination of loss which indicates agreement to better than 2 percent. Other bridge techniques for this type of measurement are reviewed.
2