Publication | Closed Access
Analysis of very fast transient overvoltages (VFTO) from onsite measurements on 800 kV GIS
43
Citations
30
References
2012
Year
Electrical EngineeringFast Transient OvervoltagesPower EngineeringEngineeringSmart GridKv GisOnsite MeasurementsStandard Voltage ShapePower System TransientComputer EngineeringSystems EngineeringElectric Power TransmissionPower ElectronicsPower System ProtectionGrid StabilityNew Vfto TypePower System Analysis
In IEC 60071-1 and 62271-102, there is neither standard voltage shape nor standard peak value for very fast transient overvoltages (VFTO). Previous work by other researchers had classified VFTO into two types. A new type was identified in this paper based on an onsite test on a commercially-operated 800 kV GIS. Disconnectors were opened/closed under real operation conditions. Characteristics of the new VFTO type were analyzed, including times of the arc restrikes between the contacts of the disconnectors, trapped charge, damping time constant, magnitude, rise rate, and oscillating frequency. The results of this paper are expected to be of help for the completion of standards on VFTO.
| Year | Citations | |
|---|---|---|
Page 1
Page 1