ASSESSMENT OF MEAN RADIANT TEMPERATURE IN INDOOR ENVIRONMENTS

Barbara E. Tredre

Occupational and Environmental Medicine · 1965 · 20 citations · 0 references

DOIFull text

Open access

Concepts

Abstract

The mean radiant temperature (m.r.t.) is usually assessed as the radiation received at a point (or by a small sphere), but it is clearly important to know how adequately this parameter describes the heat load on a man, for in the presence of hot surfaces his shape and orientation may have significant effects. This paper presents the results of experiments designed to assess the radiant heat received by a man in a controlled temperature room in which non-uniform environments were achieved by locating a heated panel either overhead or on one wall. The m.r.t. was determined with reference to a point using (<i>a</i>) the solid angle and temperature of each surface of the room, (<i>b</i>) a radiation thermopile, and (<i>c</i>) a globe thermometer. The m.r.t. was also determined with reference to (<i>a</i>) a cylinder 68 in. in height and 12 in. in diameter, and (<i>b</i>) models of standing and sitting men. It seems that in indoor environments, where there is no intense radiation from sharply localized sources, the single estimation of m.r.t. with a globe thermometer at 45 in. above the floor will generally give a satisfactory indication of the heat load on a standing or sitting man.