IEEE Transactions on Power Delivery · 1998 · 143 citations · 6 references
EngineeringElectrical EngineeringSystems EngineeringDynamical SystemsPower ElectronicsSystem DynamicsControl Of Dynamical SystemsControl SystemsControl TheoryFeedback ControlPower QualityPower System StabilityApproximate DecouplingControl ConceptInvertersNonlinearityPolesRoot Locus AnalysisSystem PolesVoltage Source Inverters
Nonlinear VSI equations and uncertain AC parameters can cause closed‑loop dynamics to deviate significantly from desired behavior. The study proposes a new dynamic control approach for FACTS devices such as STATCOM and UPFC that use voltage source inverters. The method linearizes the dq inverter model, employs high‑gain full‑state feedback to assign poles and eigenvectors, and is validated experimentally on a laboratory STATCOM with root‑locus analysis of small‑signal dynamics. Root‑locus results show that the proposed controller virtually eliminates the impact of VSI nonlinearity and keeps the effect of AC parameter variations minimal.
This paper presents a new approach for the dynamic control of FACTS apparatus, such as the STATCOM and UPFC, which utilize voltage source inverters (VSI) as their main building block. The control concept is based on a linearization of the dq inverter model. Feedforward techniques which are traditionally used for the approximate decoupling of d and q-axis control are discarded, in favour of a high gain full state feedback approach which assigns both closed loop system poles and, more importantly, their associated eigenvectors. Experimental validation of the approach is carried out on a laboratory STATCOM setup. Due to the nonlinear nature of the VSI equations and the uncertainty of AC system parameters, actual closed loop system dynamics can stray quite dramatically from those desired. Root locus analysis is therefore performed to investigate the small signal system dynamic behaviour. The loci demonstrate that the effect of system nonlinearity on the closed loop poles is virtually eliminated by the proposed control. The effect of AC system parameter variations is also shown to be minimal.
6
Linear Control System Analysis and Design
Electronics and Power · 1982 · 334 citations
Operation of ±100 MVAr TVA STATCON
C. Schauder, M.G. Gernhardt, E.J. Stacey et al. · IEEE Transactions on Power Delivery · 1997 · 139 citations
Engineering, Electrical Engineering, Critical Infrastructure Protection +12