IEEE Transactions on Industry Applications · 2013 · 57 citations · 2 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionPower ElectronicsDistributed Energy ResourcesMicrogridsPower Grid AnalysisPower System StabilityProtection SystemsVoltage RegulationDistributed GenerationDistributed Generation IntegrationMicrogrid ProtectionOperating ConditionsOvercurrent ProtectionOvervoltage ProtectionReliability Risk AnalysisReliability Risk Assessment
Distribution feeder protection could soon be complicated by nonradial flows of real and reactive power available from high penetration distributed generation and potentially from microgrids. Nondirectional overcurrent protection may not provide necessary security and sensitivity for faults on remote points of the circuit. Directional supervision is necessary to set overcurrent pickups with adequate sensitivity for remote faults. Setting the directional element by traditional means provides a reliability risk at varying VAR flows within reach of specific types of distributed generation. This paper will demonstrate the limitations of nondirectional overcurrent protection and the pitfalls of an improperly configured directional element. A unique solution using directional overcurrent elements further secured by a load encroachment function can solve these problems. This approach has been validated in renewable plant collector circuit protection applications over a wide range of operating conditions.
2
Short circuit current contribution for different wind turbine generator types
Eduard Muljadi, Nader Samaan, Vahan Gevorgian et al. · 2010 · 120 citations · Full text