Atp simulation for arc‐furnace flicker investigation

A. Cavallini, G.C. Montanari, L. Pitti, Dario Zaninelli

European Transactions on Electrical Power · 1995 · 31 citations · 8 references

Concepts

Abstract

Abstract An arc‐furnace model consisting of non‐linear, time‐varying resistance, realized by the Alternative Transients Program (ATP), is presented in this paper. It is shown that the model is appropriate for flicker investigation in electrical networks supplying arc furnaces, constituting a valid alternative to the linear arc modelling realized by amplitude modulation of voltage generators. Block diagram of the procedure for ATP modelling of the nonlinear, time‐varying arc resistance, dynamic voltage‐current characteristic of the furnace electric arc, voltage and current arc waveforms and characteristic curves of an arc furnace, obtained by ATP simulation, are presented, referring to circuit parameters taken from an actual plant and to a sinusoidal law for arc‐length time variation. Aflickermeter ATP simulation is realized to derive equivalent voltage‐variation values in agreement with the actual flicker measurements.

References

8