Journal of Chemical & Engineering Data · 1999 · 87 citations · 16 references
EngineeringChemical EngineeringChemistryHeat TransferThermal AnalysisWater TreatmentMoisture AnalysisMoisture TransportRelative HumidityDehumidificationDehumidification EfficiencyDehumidifiersDesiccant DehumidificationDesiccant SystemsDesiccated StorageExperimental Data CollectionVapor Pressure
The vapor pressures of the aqueous desiccants lithium chloride, lithium bromide, calcium chloride, ethylene glycol, propylene glycol, and their mixtures were measured at their typical operating concentrations and at temperatures from 298 K to 313 K. The experimental data were fitted to an Antoine type of equation, ln[ P (kPa)] = A − B /[ T (K) + C ], where A, B, and C are constants and are concentration dependent. Vapor pressure data were further used to predict the effectiveness of dehumidification in liquid desiccant dehumidifiers.