Publication | Closed Access
Redundant Observability PMU Placement in the Presence of Flow Measurements Considering Contingencies
104
Citations
8
References
2013
Year
Reliability EngineeringEngineeringPhasor Measurement UnitsSmart GridMeasurementPower System ReliabilityWide Area MonitoringComputer EngineeringObservability RedundancySystems EngineeringPower System ProtectionBranch Flow MeasurementsPower Systems
Phasor measurement units (PMUs) have made it possible to observe and control wide-area power systems. In this paper, a new redundant observability method as a mixed-integer linear programming (MILP) is presented for optimal PMU placement. Redundant observation of buses enhances measurement reliability. The proposed method improves observability redundancy by a new objective function while using the same number of PMUs as the existing methods. Because of using MILP, the global optimal integer solution is achieved with a zero optimality gap. In addition, a systematic novel approach is proposed to incorporate already installed branch flow measurements in the PMU placement problem leading to a reduced number of PMUs required for system observability. This approach is able to handle both single and multiple flow measurements incident to a bus. PMU placement in case of PMU failure or branch outage is also studied. The proposed method along with an existing method is tested on four IEEE and Polish 3375-bus test systems. Obtained results, discussed in detail, show the efficiency of the proposed method in both speed and accuracy.
| Year | Citations | |
|---|---|---|
Page 1
Page 1