Concepedia

Publication | Closed Access

An Improved Islanding Detection Method for a Grid-Connected Inverter With Intermittent Bilateral Reactive Power Variation

97

Citations

23

References

2012

Year

Abstract

An islanding detection method for a grid-connected inverter incorporating intermittent bilateral (IB) reactive power variation (RPV) is described. The inverter output with IB reactive power enables the detection of an islanding. The RPV range is derived in order to eliminate the nondetection zone. The design scheme of variation time in the method is obtained by estimating the transient response due to islanding occurrence. In addition, the effect of the proposed detection strategy on power quality is investigated. The proposed islanding detection method has been experimentally verified on a three-phase grid-connected 6-kW inverter.

References

YearCitations

2006

5.1K

2004

593

2007

396

2005

371

2000

331

2008

311

2000

309

2003

303

2007

288

2011

198

Page 1