2014 · 30 citations · 24 references
EngineeringElectrical EngineeringCircuit TheoryPower ElectronicsRenewable Energy SystemsAc-ac ConvertersConverter TopologiesDc-ac InvertersPower Grid AnalysisPower QualityVoltage RegulationCurrentsFilter DesignGrid-connected InvertersHarmonic ReductionPassive DampingPassive Damping DevicesPower Loss EstimationVoltage Source Inverters
LCL filter is becoming an attractive choice over conventional L filters for grid-connected voltage source inverters (VSI) due to smaller inductor size and better attenuation of the ripple components in the grid current. The modulation of the VSI generates switched voltages which results in distorted currents. In this paper, a simple closed form analytical expression is derived for the higher order switching components present in the inverter voltage. This is used in a systematic design procedure to design the LCL filter components for allowable grid current harmonics. A passive damping resistor is designed ensuring minimum power loss. The design is validated by simulations in MATLAB/Simulink and experiments on a laboratory prototype.
24