IEEE Transactions on Industry Applications · 2012 · 212 citations · 19 references
EngineeringElectrical EngineeringCircuit TheoryCritical Infrastructure ProtectionPower ElectronicsElectrical MeasurementPower Grid AnalysisPower QualityPower SystemsSmart Grid SystemsSmart GridsGridsIslanded OperationIslanded Power SystemsIslanding DetectionSmart Grid OperationsSystem Response Analysis
Islanding detection is of great importance for reliable operation of smart grids. Islanding-detection methods can be classified into three different groups, i.e., active, passive, and communication-based methods. Active methods inject a disturbing signal (typically a voltage) and analyze the system response (typically in the current). These techniques have a low nondetection zone (NDZ) but present the inconvenience inherent to injecting a disturbing signal. Passive methods monitor the grid condition from the grid variables. These techniques are easy to implement but present a large NDZ. Communication methods have the inconvenience of relying on communications, currently being of limited use. This paper proposes a new active islanding-detection method, based on the measurement of the grid high-frequency impedance by means of the injection of a high-frequency voltage. The advantages of the method are almost negligible adverse effects due to the injected high-frequency voltage and accurate and fast islanding detection, i.e., in the range of a few milliseconds. Furthermore, the estimated high-frequency impedance can be used for the adaptive control of the power converter.
19