Computation of 3-D Magnetic Leakage Field and Stray Losses in Large Power Transformer

Zhanxin Zhu, Dexin Xie, Gang Wang, Yanli Zhang, Xiuke Yan

IEEE Transactions on Magnetics · 2012 · 35 citations · 7 references

Concepts

Abstract

A time-stepping finite element method combining analytical and numerical solutions for laminated-material homogenization is proposed to calculate 3-D magnetic leakage field and its structural parts stray losses in a 380 000 kVA/500 kV single-phase power transformer, and the high-order harmonics of field components can be considered. To verify the method and computation code, a supplementary model of Team Problem P21 <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">C</sup> -M <sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">1</sub> is made. Measured and computed results to the model indicate the validity of the method proposed.

References

7