22nd International Conference and Exhibition on Electricity Distribution (CIRED 2013) · 2013 · 10 citations · 0 references
EngineeringElectrical EngineeringMaterials ScienceHeat TransferMechanical Behavior Of MaterialsThermal AnalysisElectrical InstallationJoint StrengthThermal Expansion AnalysisThermal Properties Of MaterialsThermal StressesCable Force AnalysisCable SystemsCurrent Loading On CablesFailure MechanismsPower GenerationThermal ExpansionThermo-mechanical DeformationThermo-mechanical Stress
Cable links with a high current load become more usual, especially with wind power generation and third party access to mv cable networks. Analyses of failed medium voltage joints from high loaded cable links in The Netherlands tend to indicate that thermo-mechanical forces play an important role in most failure mechanisms. Theoretically, huge forces can be expected on MV joints, due to the expansion of the conductors. In order to compare the theoretical forces with those that can actually occur during the real life of the accessories, the forces exerted by the widely used stranded compacted and solid aluminium conductors of 240 and 630 mm2 were measured. This paper presents the results of those measurements and points out that those forces are never considered during the qualification of the accessories according to the relevant standards. (4 pages)