Publication | Closed Access
Real-Time External Equivalents for Static Security Analysis
142
Citations
9
References
1979
Year
Power EngineeringEngineeringPower Grid OperationInformation SecurityReal-time External EquivalentsSoftware AnalysisFormal VerificationHardware SecuritySystems EngineeringNew MethodsStatic CheckingModeling And SimulationPower SystemsPower System AnalysisElectrical EngineeringStatic AnalysisComputer EngineeringComputer SciencePower System DynamicEquivalent ModelsPower NetworkStatic Program AnalysisData SecuritySoftware SecuritySmart GridEnergy ManagementProgram AnalysisExternal System
Equivalent models for the external system in online load-flow studies are presented. The main contribution is a simple extension to the Ward-type equivalencing method that solves the boundary-bus designation problem and gives reliable and accurate results. The method can be applied equally well for off-line equivalencing, where it overcomes the need for buffer zones. Variations on this technique are investigated. The models require topology information, but no real-time measurement data, for the external system. The new methods have been verified by simulation on the IEEE 30 and 118 bus load-flow test systems and on the 835-bus interconnected 15 GW power system of S.E. Brazil.