DC breaking tests up to 55 kA in a single vacuum interrupter

I. Benfatto, Alvise Maschio, S. Manganaro

IEEE Transactions on Power Delivery · 1988 · 20 citations · 3 references

Concepts

Abstract

DC current breaking tests were carried out on several vacuum circuit-breakers during the design of the energy transfer units for the RFX fusion experiment. The tests were performed with a synthetic circuit able to reproduce the expected stresses on the switching element during the breaking phase. The performance of a prototype for a medium-voltage AC switch with a self-produced axial magnetic field is discussed. The interrupter was found capable of breaking currents up to 55 kA with a recovery voltage greater than 35 kV and high values of di/dt in a large range of arcing times.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>