Nucleate Pool Boiling Heat Transfer of R134a and R134a-PVE Lubricant Mixtures on Smooth and Five Enhanced Tubes

Wen‐Tao Ji, Ding-Cai Zhang, Nan Feng, Jian-Fei Guo, Mitsuharu Numata, Guannan Xi, Wen-Quan Tao

Journal of Heat Transfer · 2010 · 52 citations · 22 references

Concepts

Abstract

Pool boiling heat transfer coefficients of R134a with different lubricant mass fractions for one smooth tube and five enhanced tubes were tested at a saturation temperature of 6°C. The lubricant used was polyvinyl ether. The lubrication mass fractions were 0.25%, 0.5%, 1.0%, 2.0%, 3.0%, 5.0%, 7.0%, and 10.0%, respectively. Within the tested heat flux range, from 9000 W/m2 to 90,000 W/m2, the lubricant generally has a different influence on pool boiling heat transfer of these six tubes.