HVAC&R Research · 2004 · 17 citations · 10 references
EngineeringChemical EngineeringAir ConditioningHeat TransferTransport PhenomenaGas-liquid FlowRefrigerationRefrigeration SystemsCritical TemperatureMass Flow RateMass Transfer CorrelationTube TheoryTwo-phase Flow ModelingTwo-phase Pipe Flow
A correlation was developed to predict the mass flow rate of R-12, R-134a, R-502, R-22, R-407C, and R-410A through short tubes. Short tube lengths ranged from 9.5 mm to 25.4 mm, and sharp edged diameters ranged from 1.09 mm to 1.94 mm. The correlation covered both single-phase and two-phase entrance conditions under approximately choked flow. The correlation consists of nondimensional parameters that are a function of upstream conditions, downstream conditions, short tube geometry, and critical point pressure/temperature. The correlated data were drawn from previous work and work performed during this investigation. The general form of the correlation was a function for single-phase flow multiplied by a function incorporating parameters for two-phase flow. Over 1200 data points were used to produce the correlation.
10
An Introduction to Statistical Methods and Data Analysis
Technometrics · 1994 · 5.4K citations
G.B. Wallis · International Journal of Multiphase Flow · 1980 · 153 citations