Publication | Closed Access
Algorithm comparison for high impedance fault detection based on staged fault test
63
Citations
8
References
1988
Year
Fault DiagnosisElectrical EngineeringReliability EngineeringRatio Ground RelayingEngineeringFault EstimationSoftware TestingAlgorithm ComparisonFault AnalysisStructural Health MonitoringComputer EngineeringFault DataRatio Ground RelayStaged Fault TestPower System ProtectionFault DetectionAutomatic Fault DetectionElectromagnetic Compatibility
Four high-impedance fault-detection algorithms-proportional relaying, ratio ground relaying, second-order harmonic current relaying, and third-order harmonic current relaying-were simulated by mathematical models. Relaying performances using staged fault data were then compared. Results of the fault data processing were used to distinguish the detection characteristics: fault identification, stability, threshold setting adaptability, transient recovery characteristic, and availability. The operations of a ground overcurrent relay and a ratio ground relay were also checked in the test. The results can be used as a reference for the development of a reliable high-impedance fault detector.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
| Year | Citations | |
|---|---|---|
Page 1
Page 1