IEEE Transactions on Smart Grid · 2013 · 173 citations · 28 references
EngineeringElectrical EngineeringEnergy SystemsPower ElectronicsRenewable Energy SystemsDistributed Energy ResourcesPower Grid AnalysisPower QualityRenewable Energy Power ConversionSolar Energy SystemsSolar Photovoltaic SystemsDistributed GenerationDistributed Generation IntegrationGrid-connected Photovoltaic SystemsHarmonic ReductionHarmonic ResonanceHarmonicsPhotovoltaic InvertersResidential Load Modeling
The growing prevalence of nonlinear residential loads and harmonic resonance from capacitor banks threatens power quality, prompting the use of passive or active filters, while distributed generation such as PV offers a promising alternative. This study investigates the feasibility of using photovoltaic interfacing inverters to compensate residential system harmonics. A system model incorporating residential loads and PV generation is developed, and various compensation schemes based on virtual harmonic damping impedance are analyzed and compared, including the impact of capacitor banks. Simulation results confirm that the proposed compensation strategies effectively reduce harmonics under a range of operating conditions.
The increased non-linear loads in today's typical home are a growing concern for utility companies. This situation might be worsened by the harmonic resonance introduced by the installation of capacitor banks in the distribution network. To mitigate the harmonic distortions, passive or active filters are typically used. However, with the increasing implementation of distributed generation (DG) in residential areas, using DG systems to improve the power quality is becoming a promising idea, particularly because many DG systems, such as photovoltaic (PV), wind and fuel cells, have DG-grid interfacing converters. In this paper, the potential for using photovoltaic (PV) interfacing inverters to compensate the residential system harmonics is explored. A system model including the residential load and DG is first developed. An in-depth analysis and comparison of different compensation schemes based on the virtual harmonic damping impedance concept are then carried out. The effects of the capacitor banks in the system are also studied. The effectiveness of the harmonic compensation strategies under different conditions is verified through analysis and simulations.
28
A bottom-up approach to residential load modeling
A. Capasso, W. Grattieri, R. Lamedica et al. · IEEE Transactions on Power Systems · 1994 · 490 citations