Modeling Of Thermal Responsiveness Of Automatic Sprinklers

Gunnar Heskestad, R. G. Bill

Fire Safety Science · 1989 · 25 citations · 3 references

DOIFull text

Open access

Concepts

Abstract

Predictions according to a thermal response model for sprinklers, modified to account for heat loss by conduction to the sprinkler mount, have been successfully tested against response of 13 sprinkler models in room fire experiments. Sprinkler characteristics entering the response model include the Response Time Index and a conduction parameter, both measured in a hot-air tunnel. The conduction parameter did tend to rise with increasing temperature of the mount, reflecting some departure, although not significant, from ideal behavior.

References