Concepedia

Publication | Closed Access

Analysis of the neutral conductor current in a three-phase supplied network with nonlinear single-phase loads

79

Citations

3

References

2003

Year

Abstract

This paper describes what factors (i.e., load and supply) have an important effect on the neutral conductor current. It is shown that an asymmetry up to 10/spl deg/ or an unbalance of 10% in the power supply has only a minor effect on the RMS value of the neutral conductor current. An unbalance in load conditions increases the neutral conductor current. Harmonics in the power supply voltage highly affect the RMS value of the neutral conductor current.

References

YearCitations