IEEE Transactions on Industry Applications · 2003 · 79 citations · 3 references
EngineeringElectrical EngineeringCircuit TheoryElectromagnetismPower ElectronicsCurrent LoadingElectrical TechnologyNonlinear Circuit AnalysisPower Grid AnalysisPower QualityThree-phase CircuitsBalanced Three-phase SystemsCurrent UnbalanceNeutral Current AnalysisSingle-phase LoadThree-phase Circuit ModelingThree-phase Distribution NetworksThree-phase PowerUnbalanced Three-phase Systems
This paper describes what factors (i.e., load and supply) have an important effect on the neutral conductor current. It is shown that an asymmetry up to 10/spl deg/ or an unbalance of 10% in the power supply has only a minor effect on the RMS value of the neutral conductor current. An unbalance in load conditions increases the neutral conductor current. Harmonics in the power supply voltage highly affect the RMS value of the neutral conductor current.