Transactions of the American Institute of Electrical Engineers · 1933 · 18 citations · 6 references
EngineeringMeasurementGlow DischargeEducationLaboratory MeasurementImpulse GeneratorsElectromagnetic CompatibilityPlasma ElectronicsHigh Voltage EngineeringCalibrationPulse PowerInstrumentationElectrical EngineeringImpulse VoltagesWave ShapeElectrophysiologyGas Discharge PlasmaElectronic InstrumentationInstrument DevelopmentElectrical Insulation
A brief description is given of impulse generators and the discharge circuit constants involved in obtaining impulse voltages of the desired wave shapes. The relative influences of these constants are recognized and simplified discharge circuits are given. The variations in the wave shape and the reasons for the differences in sparkover values obtained with the three test waves, ½/5, 1/10 and 1½/40, are discussed. The degree of accuracy of the sphere gap for use in measuring impulse voltages is outlined. The resistance-capacitance and the resistance-cable voltage dividers for the connection of the cathode ray oscillograph are described and their operation analyzed in detail. Both dividers are shown to be satisfactory when properly arranged. Data are given showing that the same kilovolts per millimeter on the oscillogram for widely different wave shapes can be obtained. A specimen table for recording of complete test data is suggested which, it is thought, will tend to eliminate a lack of uniformity and completeness in data previously reported.
6
Dielectric phenomena in high-voltage engineering
L.E.P. · Journal of the Franklin Institute · 1930 · 678 citations
Cathode-ray oscillographs and their uses
G.F.S. · Journal of the Franklin Institute · 1929 · 15 citations