IEEE Transactions on Power Delivery · 1992 · 88 citations · 3 references
EngineeringElectrical EngineeringCritical Infrastructure ProtectionElectric MachinesPower ElectronicsCondition MonitoringElectrical System DiagnosticsElectrical System TestingFault DetectionProtection SystemsThree-phase CircuitsOperating ConditionsProtection RelayingProtective RelayingRelay ProtectionThree-phase TransformersTransformer ModelsTransformer Protection
The authors present the design, implementation and testing of a microprocessor-based high-speed relay that correctly detects transformer winding faults. Instead of relying on the presence of harmonics to identify magnetizing inrush, it uses a nonlinear model of the transformer to determine the state of its health. One version of the relay is suitable for protecting single-phase transformers, whereas another version is for protecting three-phase transformers. A three-phase delta-wye 15 kVA transformer was used to test the relay for a variety of operating conditions. The results show that the relay performs well.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>