IEEE Transactions on Power Apparatus and Systems · 1973 · 23 citations · 2 references
EngineeringElectrical EngineeringAtmospheric ElectricityCircuit TheoryCritical Infrastructure ProtectionInsulation SystemsLightning PhysicsLightning ProtectionPower QualityPower SystemsThunderstorm ElectrificationElectric Substation ProtectionHigh-voltage InsulationHigh-voltage Power SystemsInsulation DesignLightning Protection For Power SystemsLightning Protection Of SubstationsLightning Protection SystemsTransformer Insulation
This paper presents the development of BIL (Basic Lightning Impulse Insulation Level) ratings for SF6 gas insulated substations from 72.5 kV to 765 kV. The unique properties of the gas insulated substation are analyzed and insulation coordination design techniques are utilized to determine BIL ratings for the substation equipment, other than the transformer, with a lightning arrester located at the entrance terminals. The resulting analysis shows that, in general, the required BIL level of apparatus for gas insulated systems can be lower than for conventional equipment because of lower surge impedance and shorter lengths of the gas insulated bus.
2
Traveling waves on transmission systems
T.K. Cleveland · Journal of the Franklin Institute · 1934 · 66 citations