Thermal Science · 2008 · 15 citations · 1 references
EngineeringMechanical EngineeringAir ConditioningEnergy SystemsHvac SystemsAir Conditioning EquipmentAir Conditioning SystemsEnergy ConversionHvac System DesignRefrigerationRefrigeration SystemsCompressor SystemsEnergy ConsumptionEnergy Savings AssessmentRefrigerant CapacityRefrigerant CompressorsRefrigerant MixturesRefrigerantsRefrigeration Performance Analysis
This paper presents an experimental study on the replacement of CFC12 and HFC134a by the new R290/R600a refrigerant mixture as drop-in replacement refrigerant with and without the effect of magnetic field. Without any modification to the system components drop-in experimental tests were performed on a vapour compression refrigeration system with a reciprocating compressor, which was originally designed to operate with CFC12.The test results with no magnets showed that the refrigerant R290/R600a had 19.9-50.1% higher refrigerating capacity than R12 and 28.6-87.2% than R134a. The mixture R290/R600a consumed 6.8- -17.4% more energy than R12. The coefficient of performance of R290/R600a mixture increases from 3.9-25.1% than R12 at lower evaporating temperatures and 11.8-17.6% at higher evaporating temperatures. The effect of magnetic field force reduced the compressor energy consumption by 1.5-2.5% than with no magnets. The coefficient of performance of the system was higher in the range 1.5-2.4% with the effect of magnetic field force. The R290/600a (68/32 by wt.%) mixture can be considered as an excellent alternative refrigerant for CFC12 and HFC134a systems.