IEEE Transactions on Instrumentation and Measurement · 1991 · 12 citations · 4 references
EngineeringElectrical EngineeringElectromagneticsElectromagnetismPassive DesignElectromagnetic PowerMachine WindingsMagnetic Circuit AnalysisMagnetic ComponentsExperimental Results InterpretationMagnetic Component DesignMagnetic CoresMagnetic FluxTransformer DesignTransformer TheoryWinding Design
A novel design of magnetic cores and windings of a two-stage current transformer which considerably improves its linearity and accuracy for a given load is discussed. The equations which describe the operation of the transformer are given, and formulas for the calculation of the error are derived. A practical technique for unloading the second core and bringing its magnetic flux near zero is given. Experimental results show that with relatively small cores and a small amount of copper an accuracy better then 20 ppm and 20 mu rd is achieved. The device is passive, with no electronically enhanced technique being implemented.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>
4