Improvement of the DC voltage insulation efficiency of suspension insulators under contaminated conditions

37

Citations

2

References

1988

Year

Abstract

The authors describe the results of the research and development on a suspension-type insulator having a DC contamination withstand voltage 1.25 to 1.3 times higher than that of the standard DC fog insulator, as measured by the fog-withstand or the clean-fog method. Also described are the withstand voltage characteristics of the suspension insulator contaminated with soluble materials and nonuniformly contaminated, simulating natural-field conditions. Design criteria taking these results into account are also discussed.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">&gt;</ETX>