IEEE Transactions on Power Apparatus and Systems · 1972 · 32 citations · 7 references
EngineeringElectrical EngineeringElectric MachinesElectromagneticsElectromagnetismCurrent DistributionGenerator OperationInduction MachinesLosses In Electric MachinesMagnetic Circuit AnalysisSynchronous MachinesSalient Pole Synchronous Machines
In steady‑state analysis of salient‑pole alternators, reactances Xd and Xq are usually assumed constant, but this assumption fails in saturated machines. The authors determine Xd and Xq by computing magnetic induction in the alternator’s cross‑section using University‑established difference methods, then extracting saturated reactances from flux plots, and apply this analysis to a 82.5 MVA, 16.5 kV GE alternator. The study confirms that Xd and Xq are load‑dependent.
In the steady-state analysis of salient pole alternators the reactances Xd and Xq are generally assumed to be constant. This is not the case in saturated machines. The reactances are functions of the operational regime of the alternators, and for an exact analysis of the alternator's behavior the appropriate values of Xd and Xq have to be used. The magnetic induction is found in the cross section of the alternator by difference methods established at the Universityl and then saturated Xd and Xq are determined from flux plots. The results confirm that Xd and Xq are load dependent. The analysis is applied to a General Electric alternator with nameplate data 82.5 MVA, 16.5 kV, wye-connected, 40 poles and 60 Hz.
7