IEEE Transactions on Aerospace and Electronic Systems · 1986 · 26 citations · 23 references
EngineeringElectrical EngineeringElectric MachinesPower ElectronicsSystem DynamicsControl SystemsControl TheoryGenerator OperationPower QualityPower System StabilitySynchronous MachinesCompensatorsElectromechanical TransientsExcitation ControlStatic Var CompensationSynchronous Generator OperationSynchronous Machine ControlThree-phase PowerVoltage
The design of a novel static VAR compensator for the damping of electromechanical oscillation in a synchronous generator is presented. The proposed compensator, which is made up of a fixed capacitor and a thyristor-controlled inductor, is installed at the generator terminal to provide the required damping without deteriorating the voltage profile under disturbance conditions. In order to have better dynamic performance, a supplementary proportional-integral-derivative (PID) controller of which the parameters are determined by eigenvalue assignment is incorporated in the static VAR compensators. The dynamic responses of the synchronous machine subjected to a three-phase fault are given to demonstrate the effectiveness of the static VAR compensators. A comparison study of the proposed controller and a PID excitation controller is made with respect to damping enhancement and terminal voltage deviation.
23
Power System Control and Stability
F.M. Hughes · Electronics and Power · 1977 · 1.4K citations
Engineering, Electrical Engineering, Systems Engineering +12
Pole assignment by gain output feedback
Hidenori Kimura · IEEE Transactions on Automatic Control · 1975 · 520 citations