IEEE Transactions on Power Delivery · 1988 · 34 citations · 4 references
EngineeringElectrical EngineeringCircuit TheoryEnergy SystemsPower ElectronicsAc-dc ConversionAc-dc ConvertersDc-dc ConversionDc-dc ConvertersLoss AssessmentLoss QuantificationCurrentsHarmonic Loading EffectsHarmonic ReductionLoad-dependent LossesLoss AnalysisPower Loss ModelingShort-circuit PowerThree-phase Transformers
Losses were measured during short-circuit tests on a 262.5 MVA, three-phase, five limb converter transformer at various frequencies from 50 Hz to 1 KHz. Using these and the calculated values of the harmonic currents produced by the AC/DC converter, load losses were determined. Variations of these losses with the converter firing angle, with the transformer reactance and with the load were studied. A simple method of loss calculation which has the potential for application at the design stage was developed.< <ETX xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">></ETX>