Science and Technology for the Built Environment · 2015 · 26 citations · 3 references
EngineeringArchitectural EngineeringBuilding ScienceAir ConditioningHeat TransferHvac SystemsAir Conditioning EquipmentAir Conditioning SystemsBuilding Cooling SystemsCooling SystemsRefrigeration SystemsThermal InsulationAbsorption CoolingAbsorption Cooling SystemsAir Cooling SystemsDehumidificationDesiccant DehumidificationDesiccant SystemsEnergy ConsumptionLatent Cooling Load
Air-conditioning demand, especially in hot and humid climates, causes most of the energy consumption in buildings. In these applications, the latent load often constitutes a significant part of the total load. Conventional air-conditioning systems deal with the required dehumidification by cooling the moist air below its dew point and reheat it later to increase its temperature to comfortable supply conditions. By using solid/liquid desiccant systems, which absorb humidity from the air, it becomes unnecessary to reach the dew point to dehumidify, thereby reducing energy consumption. In liquid desiccant systems, dehumidification occurs in the absorber, where the humidity of the air is absorbed by direct contact with a desiccant. Most of the previous liquid desiccant system studies have used adiabatic absorbers, where the solution must be cooled externally before being delivered into the air-solution contactor. However, based on experience with closed-cycle absorption systems, internally cooled absorbers are expected to yield better performance considering that a cool solution temperature throughout the absorber will maintain a constant and low vapor pressure. This article presents an experimental study of two different internally cooled air-solution contactors using falling-film tubular heat exchangers: The tubes in one are made of titanium and in the other of high-density poly ethylene. The experiments have been conducted in a liquid desiccant system under summer conditions in the Mediterranean city of Haifa, Israel. A performance comparison is also carried out with an externally cooled air-solution contactor, using results obtained from previous studies.
3