IEEE Transactions on Power Apparatus and Systems · 1976 · 27 citations · 7 references
EngineeringElectrical EngineeringPhysicsBlastingCircuit TheoryPlasma PhysicsBlast DesignBlast MonitoringArc DischargesExperimental Results InterpretationVoltage
With a model SF <inf xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</inf> gas blast interrupter, arc extinction performance was investigated. The measurements were carried out for di/dt values ranging from 13 ∼ 27 A/µs, for RRRV extending from 3.5∼ 13.0kV/µs and for a fixed pressure of 15kg/cm <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sup> . On the other hand, the voltage and current wave forms near current zero in the short line fault (SLF) test circuit were calculated employing Mayr's equation and the interrupting capability was investigated using the arc time constant and arc voltage obtained from the experimental results. From this calculation, the following relation was found. RRRVc ∞ (i)- <sup xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">(2.2∼2.45)</sup> . The theoretical calculation was found to coincide satisfactorily with the experiments.
7